SERVICE MANUAL #07
Instructions For The Troubleshooting
And Repair Of All Traulsen TE-Series
Refrigerated Equipment Stand Models
FORM NUMBER TR35896 - REVISED. 4/08
-NOTICE-
This Manual is prepared for the use of trained Authorized Traulsen Service Agents and should not be used
by those not properly qualified. This manual is not intended to be all encompassing, but is written to
supplement the formal training, on-the-job experience and other product knowledge acquired by Autho-
rized Traulsen Service Agents. Before proceeding with any work, you should read, in its entirety, the repair
procedure you wish to perform to determine if you have the necessary tools, instruments and skills required
to perform the procedure. Procedures for which you do not have the necessary tools, instruments and
skills should be performed only by a trained Authorized Traulsen Service Agent.
Reproduction or other use of this Manual, without the express written consent of Traulsen, is prohibited.

Questions and Answers

  • J
    Jeffrey LaneAug 12, 2025
    Why is the compressor run time lengthy on my Traulsen TE?
    • M
      Michael MckinneyAug 13, 2025
      If your Traulsen Refrigerator's compressor runs for a long time, several factors could be responsible. Begin by checking for a partial loss of refrigerant and ensuring that ambient conditions are not excessively high. Inspect the condenser for dirt or airflow obstructions. Avoid overloading the refrigerator with excessive product and minimize frequent drawer openings. Make sure the drawer gasket is in good condition. Other potential causes include issues with the INTELA-TRAUL control, contaminants in the system, compressor valve leakage, and the defrost cycle's effectiveness.
  • T
    Tamara CochranAug 16, 2025
    Why is my Traulsen TE in continuous unit operation?
    • M
      Mr. Willie OwensAug 16, 2025
      If your Traulsen Refrigerator is running continuously, check for a loss of refrigerant or excessive drawer openings. Inspect the INTELA-TRAUL control and compressor valves for any issues. A dirty condenser or filter, as well as a high 'DL' temperature, can also cause continuous operation.
  • T
    thomas40Aug 20, 2025
    What to do if compressor short cycles on overload in Traulsen TE?
    • N
      Nicholas ZamoraAug 20, 2025
      If the compressor in your Traulsen Refrigerator is short cycling on overload, examine the unit for low voltage and check the refrigerant charge. A dirty condenser coil or filter, wiring issues, a faulty condenser fan, a malfunctioning run capacitor or start components, issues with the INTELA-TRAUL control, and excessive head pressure could also be the cause.
  • L
    Laura HansenAug 25, 2025
    How to fix low suction pressure on Traulsen Refrigerator?
    • J
      Jeffrey ReyesAug 25, 2025
      To troubleshoot low suction pressure in your Traulsen Refrigerator, start by checking for a capillary tube restriction or a plugged drier. Also, look for signs of refrigerant loss, poor air flow, or an iced evaporator coil.
  • K
    Kelly RobertsonAug 27, 2025
    What to do if Traulsen Refrigerator will not defrost?
    • A
      Ann MooreAug 27, 2025
      If your Traulsen Refrigerator will not defrost or the defrost is inadequate, check for a malfunctioning defrost heater and any wiring issues. Also, inspect the cabinet for air leaks and check the coil sensor for failure. Issues with the INTELA-TRAUL control could also be the cause.
  • J
    Jordan PerezAug 31, 2025
    Why does my Traulsen TE compressor short cycle?
    • A
      Angela GonzalezAug 31, 2025
      If the compressor in your Traulsen Refrigerator is short cycling, check for improper air flow over the evaporator coil and ensure ambient conditions are suitable. Issues with the INTELA-TRAUL control, bad sensors, and temperature differential could also be the cause.
  • R
    rjohnsonSep 4, 2025
    What to do if Traulsen Refrigerator compressor won't run and trips overload?
    • E
      Elizabeth YuSep 4, 2025
      If the compressor in your Traulsen Refrigerator will not run, and the current draw trips the overload, check for low voltage and start component malfunction. Also, inspect the compressor windings, check for a locked rotor, and examine the discharge pressure.
  • D
    Donna BlakeSep 8, 2025
    How to troubleshoot Traulsen TE Refrigerator compressor with no current?
    • K
      Kenneth TurnerSep 8, 2025
      If the compressor in your Traulsen Refrigerator will not run and has no current draw, examine the main circuit breaker and compressor overload. Also, check the cabinet temperature and wiring. Inspect the INTELA-TRAUL control, start components, and compressor motor windings.