TINYPRO6 – Operational Manual
TRINITY
[5]
Technical Specifications
SR.
NO
PARAMETERS
&
OPTIONS
STATASTICS
1 Volts R-N
Direct Voltage Input : Up to 300V L-N
Burden : 0.5VA
Secondary Voltage Input : 63.5V*
2 Volts Y-N
3 Volts B-N
4 Volts RY
Direct Voltage Input : Up to 500V L-L
Burden : 0.5VA
Secondary Voltage Input : 110V*
5 Volts YB
6 Volts BR
7 Current R
Secondary Current Input : 5A or 1A (To be specified at the
time of Ordering)
CT Primary : Site Selectable
Range of Reading : 0 – 4000A
Burden : < 1.0VA
Overload(Through CT) : 5A CT = 6A RMS Continuous
1A CT = 1.2A RMS Continuous
(Whole Current) : 120% of Imax continuous.
8 Current Y
9 Current B
10 Frequency
45 to 55 Hz, Accuracy : 0.3% of Reading
11 KWh Range of Reading : 0 to 99999999.9 kWh
Accuracy : 1.0S as per IS13779.
14 System PF Accuracy : 1% of Reading (IPFI>0.5)
Range of Reading : 0.05 to 1.00 Lag/Lead
16 System KW Accuracy : 1.0% of Reading
(Between 0.5 Lag to 0.8 Lead)
18 DISPLAY
0.4” Red Seven Seg.
19 RS485
For Integration with EMS/SCADA
20 Bezel 96x96 mm
DIN enclosure
21 Depth 55 mm