TFP610
Page 13 of 28
Attic Spaces Greater Than 60 Feet (18,3m) up to 80 Feet (24,4m) Wide, (Ref. Figures 14 & 15)
Only 8.0 K, BB Sprinklers in conjunction with AP Sprinklers or Standard Spray Sprinklers can be used to protect attics up
to 80 feet (24,4 m) wide.
NOTE
Attics over 80 feet (24,4 m) wide must use Standard Spray Sprinklers throughout because Attic Sprinklers have not been
tested in this scenario.
For single ridge construction (Ref. Figure 14A & 14B), use 8.0K, BB Sprinklers to protect the center portion. AP Sprinklers
(Ref. Fig. 14A) or Standard Spray Sprinklers (Ref. Fig. 14B) are then used to protect up to 10 feet (3,1 m) of width at the
eaves beyond the maximum allowable 60 foot (18,3 m) span of the 8.0K, BB Sprinklers.
For hip roof construction (Ref. Figure 15), use 8.0K, BB Sprinklers in the center portion and HIP Sprinklers can be located
down the entire hip. AP Sprinklers or Standard Spray Sprinklers are then used to protect up to 10 feet (3,1 m) of width at
the eaves beyond the maximum allowable 60 foot (18,3 m) span of the 8.0K, BB Sprinklers, and the maximum allowable
horizontal coverage of the HIP Sprinklers.
10'-0" MAX.
(3,05 m)
AP
SPRINKLER
COVERAGE
AP
SPRINKLERS
SPACED
8'-0" (2,4 m)
TO
7'-0" (1,8 m)
ON CENTER
6'-0" MAX.
(1,83 m)
4'-0" MIN.
(1,22 m)
6'-0"
(1,83 m)
MAX.
BB ATTIC
SPRINKLER
SEE FIG. 11
BB SPAN
(TABLE A)
10'-0" MAX.
(3,05 m)
AP SPRINKLER
COVERAGE
SD ATTIC
SPRINKLER
6'-0" MAX.
(1,83 m)
4'-0" MIN.
(1,22 m)
6'-0"
(1,83 m)
MAX.
SEE FIG. 11
AP
SPRINKLERS
SPACED
8'-0" (2,4 m)
TO
7'-0" (1,8 m)
ON CENTER
SD SPAN
(TABLE A)
BB
SPAN
(TABLE A)
10'-0"
(3,0 m)
10'-0"
(3,0 m)
PERIMETER
PROTECTION
AREA
HIP
SPRINKLERS
BACK
TO BACK
SPRINKLERS
ROOF
SLOPE
10'-0"
(3,0 m)
HIP
SLOPE
AP
SPRINKLERS
AT THE EAVES
HIP
RIDGES
RIDGE
LINE
CPVC PIPE MAY
BE USED IN SHADED
AREA FOR CEILING
PROTECTION BELOW
(SEE PAGE 6)
7'-0" to 10'-0"
(2,1 m to 3,0 m)
ON CENTER FOR
AP SPRINKLERS
FIGURE 14A
FIGURE 14B
FIGURE 15