FIGURE 4   
MINIMUM RADIUS INDICATOR 
MRI55
TFP720
Page 8 of 10 
Installation
The  Tyco
®
  FASTFLEX  Flexible  Sprin-
kler  Hose  as  shown  in  Figure  1,  is 
to  be  installed  with  the  following 
instructions. 
NOTICE
Flexible  Hoses  are  intended  only  to 
connect  sprinklers  directly  to  system 
piping; for an example, refer to Figure 
1. Flexible Hoses cannot be joined to-
gether  to  form  longer  hoses.  Joining 
Flexible Hoses together creates an as-
sembly  with  “unknown  performance” 
that  has  not  been  accounted  for  in 
system  calculations  or  safe  product 
performance.
Step  1.  Review  the  Design  Criteria 
section  that  applies  to  the  Approval 
agency  recognized  by  the  authority 
having jurisdiction, as well as Figure 3 
that provides “Installation Guidance”.
Step  2.  Determine  the  approximate 
place where the sprinkler will be locat-
ed.  The  Support  Bar  is  700  mm  long 
and shall be mounted on the 600 mm 
width of the ceiling grid. The sprinkler 
should be located as close as possible 
to the center of the  distance between 
ceiling grid t-bars. 
Step  3.  Slide  the  Reducer  Bracket 
onto  the  Support  Bar.  Loosely  attach 
the Reducer Bracket and the two Bar 
Fixing Clamps on the Support Bar and 
place the Bar Fixing Clamps such that 
the  Support  Bar  crosses  the  location 
where the sprinkler will be located.
Step 4. Attach one end of the Flexible 
Hose  onto  the  sprinkler  reducer.  Ap-
plying the wrench to the Slip Nut, and 
not  to  the  Flexible  Hose,  tighten  to  a 
maximum torque of 35 Nm.
Step  5. Attach the Inlet Nipple on to 
the branch  line. Ensure  that the arrow 
is  in  the  appropriate  direction  of  flow 
to the sprinkler and to use pipe thread 
sealant at the connection to the branch 
line. 
Attach one end of the Flexible Hose on 
to the Inlet Nipple. Applying the wrench 
to the Slip Nut, and not to the Flexible 
Hose, tighten to a maximum torque of 
35 Nm. Do not twist the Flexible Hose. 
Step 6. Bend the Flexible Hose into a 
curve(s) that locates the Sprinkler Re-
ducer  at  the  other  end  of  the  Flexible 
Hose  in  the  area  where  the  sprinkler 
will  be  located.  The  tube  arc  should 
not be twisted, and the arc should be 
as large and smooth as possible. 
NOTICE
For minimum bend criteria, refer to the 
Design Criteria section  that  applies to 
the Approval agency recognized by the 
authority having jurisdiction.
A  bend  radius  smaller  than  provid-
ed  by  the  minimum  bend  criteria 
may  adversely  effect  the  friction  loss 
specifications  stated  by  the  approval 
laboratory. 
For  assembly  lengths  greater  than 
1800  mm  the  Flexible  Hose  shall  be 
supported  to  the  structure  to  ensure 
that the maximum unsupported length 
does  not  exceed  1800  mm.  In  these 
cases,  it  is  recommended  that  the 
tube  be  secured  to  a  fixed  mounting 
point  every  600  mm,  in  order  to  pro-
vide a more stable installation. 
For  installations  per  LPCB,  all  bends 
greater  than  45°  shall  be  tted  with  a 
MRI55  Plastic  Clip  Minimum  Radius 
Indicator (Refer Figure 4).
Step  7.  Insert  the  Sprinkler  Reducer 
into  the  Reducer  Bracket.  Locate  the 
Reducer  Bracket  and  Sprinkler  Re-
ducer where the  sprinkler will be, and 
loosely tighten the Butterfly Bolt on the 
Reducer Bracket.
Step  8.  Attach  the  sprinkler  to  the 
Sprinkler Reducer. Put a wrench on the 
Sprinkler  Reducer  to  counteract  the 
tightening torque and prevent the Flex-
ible Hose from twisting. Reference the 
sprinkler manufacturer’s sprinkler data 
sheet for appropriate sprinkler tighten-
ing torque, sprinkler wrench, and other 
guidance. 
Step  9.  Verify  that  the  Sprinkler  Re-
ducer is seated in the Reducer Brack-
et.  Precisely  locate  the  sprinkler  in 
all  three  axes  in  accordance  with  the 
sprinkler  manufacturer’s  data  sheet. 
Tighten  the  Butterfly  Bolts on  the  Bar 
Fixing Clamps and the Reducer Brack-
et.  The  tightening  torque  for  the  Bar 
Fixing Clamp fastener is 4,5 to 5,7 Nm, 
and  the  tightening  torque  for  the  Re-
ducer  Bracket fastener,  is  a  minimum 
of 2,3 Nm. 
Step  10. After tightening all the But-
terfly  Bolts, verify  that  the  sprinkler  is 
properly  located  in  accordance  with 
the  manufacture’s  instructions.  If  not, 
loosen the Butterfly Bolts and readjust 
as required.
Care and  
Maintenance
The  owner  is  responsible  for  the  in-
spection, testing, and  maintenance  of 
their fire protection system and devic-
es  in  compliance  with  this  document, 
as  well  as  with  the  applicable  stan-
dards of the authorities having jurisdic-
tion. The installing contractor or prod-
uct manufacturer should be contacted 
relative to any questions. 
It is recommended that automatic sprin-
kler systems  be  inspected, tested,
 and 
maintained  by  a  qualified  Inspection 
Service  in  accordance  with  local  re-
quirements and/or national codes.
NOTICE
Before closing a fire protection system 
control valve for inspection or mainte-
nance work on the fire protection sys-
tem that it controls, permission to shut 
down  the effected fire protection  sys-
tem  must  first  be  obtained  from  the 
proper  authorities  and  all  personnel 
who  may  be  affected  by  this  action 
must be notified. 
After  placing  a  fire  protection  system 
in service, notify the proper authorities 
and advise those responsible for moni-
toring  proprietary  and/or  central  sta-
tion alarms.
FLEXIBLE
HOSE
YN25
INDICATOR
RADIUS
MINIMUM
MRI55