EasyManua.ls Logo

Tyco IR6003/7 - Commissioning; Operating Parameters; Detector; P-UIM

Tyco IR6003/7
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. Commissioning
Once the Detector has been installed correctly by connecting it to the hazard monitoring system via the P-UIM, the user should
power up the detector loop and perform the following confidence checks
1. The Detector LED blips ON briefly as it receives power from the P-UIM. The P-UIM LIFE indicator is flashing and the OUTPUT
ON indicator is ON steady all other indicators are extinguished.
2. Wait 20 seconds and check that the status detailed in step 1 above remains unchanged.
3. Block the Detector Beam path for 1-minute and check that the detector signals a beam blocked state (LED flashes ON for
2-seconds). The P-UIM BEAM BLOCKED indicator is lit steady. Remove obstruction from the beam path.
4. Initiate a short reset and check that the P-UIM returns to the status detailed in step 1.
5. Initiate a long reset with the beam path blocked and check that Detector indicates a LIFE fault (LED is lit steady). The P-UIM
LIFE Indicator is lit steady. Remove the obstruction from the beam path.
6. Initiate a long reset and check that the P-UIM returns to the status detailed in step 1.
7. Operating Parameters
7.1 Detector
The Detector receives its dc supply from the P-UIM and provides status to the P-UIM as follows:
1. A normal/healthy detector input condition is indicated when the current is >20 mA and <32 mA (nominally 25 mA). The LED on
the front of the detector will be extinguished.
2. A low alarm condition is indicated when the current pulses from normal to 42 mA with a 1 second equal mark space ratio for a
period of 30-seconds.
3. A high alarm condition is indicated when the current pulses from normal to 42 mA with a 0.5 second equal mark space ratio for
a period of 2-minutes.
4. A beam blocked condition is indicated when the current switches from normal to 17 mA for a period of 2-seconds.
5. A cleaning fault condition is indicated when the current switches from normal to 17 mA for a period of 4-seconds.
6. A life fault condition is indicated when the current falls to 17 mA for >5-seconds.
7.2 P-UIM
The P-UIM supplies the detector circuit and monitors the current in the detector loop to determine the detector status as follows:
1. An open circuit condition is detected if the current is <6.3 mA for >2 seconds. 2. A normal/healthy detector input condition is
when the current is >20 mA and <28 mA.
3. A low alarm condition is detected when the current pulses from normal to >28 mA and <42 mA with a 1 second equal mark
space ratio for a period of 5 seconds.
4. A high alarm condition is detected when the current pulses from normal to >28 mA and <42 mA with a 0.5 second equal mark
space ratio for a period of 5 seconds.
5. A beam-blocked condition is detected when the current switches from normal to <16 mA for a period of 2 seconds. The fault
detection-monitoring period is 5 seconds from the receipt of the fault state.
6. A cleaning fault condition is detected when the current switches from normal to <16 mA for a period of 4 seconds. The fault
detection-monitoring period is 5
Seconds from the receipt of the fault state.
7. A life fault condition is detected when the current falls to <16 mA for >5 seconds. The fault detection-monitoring period is 5
seconds from the receipt of the fault state.
8. A short circuit condition is detected if the current increases to >74 mA for >5 seconds. The fault detection-monitoring period is 5
seconds from the receipt of the fault state. Power is removed from the detector
Note:
When the alarm or fault condition has been rectified the P-UIM and Detector should be reset.
11 / 12

Related product manuals