The Tyco Intelligent Oil Mist/Smoke Detector system consists of an IR6003/x Oil Mist/Smoke Detector and a 6005/x Power
Universal Interface Module (P-UIM).
The Oil Mist/Smoke Detector has been designed to be highly sensitive to the presence of Oil & Kerosene mists or smoke particles
in the path of the detector beam. The detector has been developed for use in enclosed oil rig wellheads areas, generator rooms
and turbine enclosures. The detector automatically compensates for contamination of the detector lenses and signals when a point
is reach where further deterioration cannot be tolerated and the lenses require cleaning. Two levels of alarm status are provided a
“Low” (pre-warning) and “High” level. Also a “Beam Blocked” status is provided in the event that the beam is interrupted.
The P-UIM, converts the output signals from the Oil Mist/Smoke Detector to 5 sets of volt free contacts, which provide the
detector status for the following conditions:
“Fault”
“Clean” (Clean detector lenses)
“Beam Blocked”
“Low” Level alarm
“High” Level Alarm
1. Introduction
2. Features
2.1 Detector
Automatic Self-Calibration.
Range 2 to 30 metres.
Weather Proof to IP65.
Certified Intrinsically Safe.
Robust Design.
Heavy duty mounting bracket available.
Independent block output.
Cleaning status output.
Dual automatic compensation.
2.2 P-UIM
Wide operating voltage range; with internal voltage regulation.
Ability to accept direct input from the detector or input from the detector via a barrier.
Remote reset feature.
Alarm/Fault volt-free output contacts.
Local indication of P-UIM and Detector status.
Screw or DIN rail mounting.