Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, VdS, and NYC Approved.
(Refer to Table A for complete ap-
proval information including corrosion
resistant status.)
Maximum Working Pressure
RefertoTableB.
Discharge Coefficient
K=2.8GPM/psi
1/2
(40,3 LPM/bar
1/2
)
K=5.6GPM/psi
1/2
(80,6 LPM/bar
1/2
)
K = 8.0 GPM/psi
1/2
(115,2 LPM/bar
1/2
)
Temperature Ratings
RefertoTableA.
Finishes
Sprinkler: Refer to Table A.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame . . . . . . . . . . . . . Bronze
Button......... Brass/Copper
SealingAssembly ..........
. . . . . Beryllium Nickel w/Teflon†
Bulb...............Glass
Compression Screw . . . . . Bronze
Deflector ...........Copper
Bushing (K=2.8) . . . . . . . Bronze
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-B Pendent and Upright
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules rec-
ognized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM’s Loss Prevention
Data Sheets). Only the Style 10 or 40
Recessed Escutcheon, as applicable,
is to be used for recessed pendent
installations.
TFP151
Page 5 of 8
TYPE NATURAL
BRASS
CHROME
PLATED
WHITE
POLYESTER
SPRINKLER FINISH
RECESSED PENDENT
(TY3251)
NOTE:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL); and, the Approval by the City of New York.
TABLE B, MAXIMUM WORKING PRESSURE
WAX OVER
LEAD COATED
LEAD
COATED
WAX
COATED
175 PSI (12,1 BAR)
5.6
1/2"
NPT
PENDENT (TY3251)
and
UPRIGHT (TY3151)
RECESSED PENDENT
(TY4251)
8.0
3/4"
NPT
PENDENT (TY4251)
and
UPRIGHT (TY4151)
8.0
1/2"
NPT
PENDENT (TY4951)
and
UPRIGHT (TY4851)
K
250 PSI (17,2 BAR)
OR
175 PSI (12,1 BAR)
(SEE NOTE 1)
175 PSI (12,1 BAR)
PENDENT (TY1251)
and
UPRIGHT (TY1151)
2.8
1/2"
NPT
175 PSI (12,1 BAR)
175 PSI (12,1 BAR)
175 PSI (12,1 BAR)
N/A
N/A
N/A
† DuPont Registered Trademark