Remote Booster Power Supply Technical Reference Manual 21
Wire routing
Separate power-limited from nonpower-limited wiring. Wiring within the enclosure
should be routed around the perimeter of the enclosure, not across the circuit
board.
Figure 10: Wire routing
(4)
(4)
(3)
(2)
(1)
Legend
(1) Power-limited wiring area
(2) Route AC supply through knockouts in nonpower-limited area
(3) Battery wiring
(4) Battery
Notes
Maintain 0.25 in. (6 mm) spacing between power-limited and nonpower-limited wiring.
NAC circuits are power-limited and supervised for opens, shorts, and overcurrents. When
configured as auxiliary power circuits, they are power-limited and supervised for shorts and
overcurrents.
Source must be power-limited. Source determines supervision.
Position the battery terminals towards the door.