Remote Booster Power Supply Technical Reference Manual 33
Legend
(1) NAC1/AUX1
(2) NAC2/AUX2
(3) NAC3/AUX3
(4) NAC4/AUX4
(5) 200 mA AUX Continuous
(6) Sense 1 IN
(7) Sense 1 COM
(8) Sense 1OUT
(9) Sense 2 IN
(10) Sense 2 COM
(11) Sense 2 OUT
(12) Trouble NO
(13) Trouble COM
(14) Trouble NC
(15) Notification appliance circuit (NAC)
(16) UL listed EOL 15 k
(17) From existing fire alarm panel
notification circuit or CC1(S) module
(18) Out to EOL or next device
(19) NAC circuit
(20) UL listed EOL 15 k
(21) Data out to next device
(22) Data in from previous device or
Signature controller
(23) NAC circuit
(24) UL listed EOL 15 k
(25) EOL 15 k, when used as a NAC
(26) UL listed EOL relay
(27) EOL 47 k
Notes
• When a booster power supply output is programmed as an AUX output, a listed EOL relay
(PAM1, 6254A-003, or 73402A) or equivalent must be used to supervise the AUX output.
• When a booster power supply output is programmed as an NAC output, a 15 k EOL resistor
must be used for supervision.