Maintenance
Page 33 of 42
7. Attach the new power supply module to the case with the screw a7/d7 provided for that
purpose.
8. On a CryptoServer LAN V4 variant c (Figure 2 resp. Figure 6), attach the guard bracket
a17/d15 to the case with the screw to protect both power supply modules against
inadvertent displacement during transport/movement. If you are using a CryptoServer
LAN V4 variant b (Figure 1 resp. Figure 5), skip this step.
9. Plug the power cable into the new power supply module a3/d3.
10. Switch on the power supply module with the power supply switch a5/d5.
If you have installed the power supply module correctly and provided it with power, the green
control light above the power supply switch a5/d5 lights up.