4.2 Commissioning and startup wizard
4.2.1 Commissioning steps:
4.2.2 Startup wizard
Vacon 20 runs the startup wizard in first power-up. The wizard can be run by setting
SYS Par.4.2 =1. The following figures show the procedure.
NOTE! Running the startup wizard will always return all parameter
settings to their factory defaults!
NOTE! StartUp-Wizard can be skipped after pressing STOP button
continuously for 30 seconds
1. Read safety instructions on page 1
7. Perform test run without motor, see the
User Manual at http://drives.danfoss.com/
knowledge-center/technical-documentation/
2. Secure the grounding and check that cables
comply with requirements
8. Run no-load tests without motor being con-
nected to the process
3. Check quality and quantity of cooling air 9. Perform an identification run (Par. ID631)
4. Check that all start / stop switches are in
STOP position
10. Connect the motor to the process and per-
form test run once again
5. Connect the drive to mains 11. Vacon 20 is now ready for use
6. Run the Startup wizard and set all necessary
parameters
Table 3: Commissioning steps