46 vacon monitoring & parameters
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
5
NOTE! These parameters are shown, when P17.2 = 0.
5.18 Motor c (Control panel: Menu PAR -> P16)
5.19 Easy usage menu (Control panel: Menu PAR -> P17)
P15.22
Temperature
min value
-50.0/
223.2
P15.23 0.0 1706
Temperature min value for
PID and frequency refer-
ence scale, hidden until an
OPTBH board is connected
P15.23
Temperature
max value
P15.22
200.0/
473.2
100.0 1707
Temperature max value for
PID and frequency refer-
ence scale, hidden until an
OPTBH board is connected
Code Parameter Min Max Unit Default ID Note
P16.1
Motor Preheat
Function
02 01225
0 = Not used
1 = Always in stop state
2 = Controlled by digital
input
P16.2
Motor Preheat
Current
0
0.5 x
I
Nunit
A 0 1227
DC current for preheating
of motor and drive in stop
state. Active in stop state
or by digital input while in
stop state.
Table 21: Motor Preheat
Code Parameter Min Max Unit Default ID Note
Application Type 0 3 0 540
0 = Basic
1 = Pump
2 = Fan drive
3 = High Torque
NOTE! Visible only when
Startup wizard is active.
P17.2
Parameter
conceal
0 1 1 115
0 = All parameters visible
1 = Only quick setup parame-
ter group visible
P17.3
Temperature
unit
0 1 0 1197
0 = Celsius
1 = Kelvin
NOTE! Hidden until an OPTBH
board is connected
Code Parameter Min Max Unit Default ID Note
Table 20: PID control parameters
P17.1

Other manuals for Vacon 20

Related product manuals