P2.19 Protocol 1 2 1 14230
Active Protocol.
1= ModbusTCP,
2= ProfinetIO
3=EtherNet/IP
P2.20 IP Address Mode 1 2 2 14231
IP mode. 1=DHCP,
2=fixed.
When in DHCP
mode,the IP address
cannot be changed
manually
P2.21 IP Part1 1 223 192 14180 IP Address Part1
P2.22 IP Part2 0 255 168 14181 IP Address Part2
P2.23 IP Part3 0 255 0 14182 IP Address Part3
P2.24 IP Part4 0 255 10 14183 IP Address Part4
P2.25 Subnet Mask P1 0 255 255 14184 Subnet Mask Part 1
P2.26 Subnet Mask P2 0 255 255 14185 Subnet Mask Part 2
P2.27 Subnet Mask P3 0 255 0 14186 Subnet Mask Part 3
P2.28 Subnet Mask P4 0 255 0 14187 Subnet Mask Part 4
P2.29 Default GW P1 0 255 192 14188
Default Gateway
Part1
P2.30 Default GW P2 0 255 168 14189
Default Gateway
Part2
P2.31 Default GW P3 0 255 0 14190
Default Gateway
Part3
P2.32 Default GW P4 0 255 1 14191
Default Gateway
Part4
P2.33 Comm.Timeout 0
65535
10 14200 Comm.Timeout
P2.35 EIP Output Instance 1
8
2 14251
Ethernet I/O Output
assemley instance.
1=20; 2=21; 3=23;
4=25; 5=101; 6=111;
7=128; 8=131.
P2.36 EIP Input Instance 1
8
2 14252
Ethernet I/O Input
assemley instance.
1=70; 2=71; 3=73;
4=75; 5=107; 6=117;
7=127; 8=137.
Code Parameter Min Max Default ID Note
Table 23: System parameters