EasyManua.ls Logo

Vacon 20 - Page 57

Vacon 20
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56 vacon general data
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7
EMC
Immunity Complies with EN50082-1, -2, EN61800-3
Emissions(See
detailed descrip-
tions in Vacon 20
User Manual at:
http://drives.dan-
foss.com/knowl-
edge-center/
technical-docu-
mentation/)
230V : Complies with EMC category C2; With an internal RFI filter.
MI4 and 5 complies C2 with an optional DC choke and CM choke.
400V: Complies with EMC category C2; With an internal RFI filter
MI4 and 5 complies C2 with an optional DC choke and CM choke.
Both: No EMC emission protection (Vacon level N): Without RFI filter
Standards
For EMC: EN61800-3,
For safety: UL508C, EN61800-5
Certificates
and manu-
facturers
declara-
tions of
conformity
For safety: CE, UL, cUL, KC
For EMC: CE, KC
(see unit nameplate for more detailed approvals)
Cable and fuse
requirements
(See detailed data
in Vacon 20 User
Manual at:
www.vacon.com)
380 - 480 V, 3~
208 – 240 V, 3~
Frame Fuse (A)
Mains cable
Cu (mm
2
)
Terminal cable min-max
(mm
2
)
Main Earth
Control
and relay
MI1 6
3*1.5+1.5 1.5-4
0.5-1.5
MI2 10
MI3 20 3*2.5+2.5 1.5-6
MI4
20
25
40
(20 and 40 is
only for 208 -
240 V, 3~)
3*6+6 1-10Cu 1-10
MI5 40 3*10+10
2.5-50
Cu / Al
2.5-35
115 V, 1~
MI2 20 2*2.5+2.5
1.5-4
MI3 32 2*6+6
208 – 240, 1~
MI1 10 2*1.5+1.5
MI2 20 2*2.5+2.5
MI3 32 2*6+6 1.5-6
600 V
MI3 6
3*1.5+1.5 1.5-4
MI3 10
MI3 20 3*2.5+2.5 1.5-6

Other manuals for Vacon 20