60 vacon general data
Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
7
Note 1: The input currents are calculated values with 100 kVA line transformer supply.
Note 2: For PM motor, please select the drive power rating according to motor shaft
power, not rated current.
Quick Modbus setup
Mains voltage 600 V, 50 / 60 Hz, 3~ series
Fre-
quency
converter
type
Rated loadability
Motor shaft
power
Nominal
input
current
Mechanical
size
Weight
(kg)
100% contin.
current I
N
[A]
150% over-
load current
[A]
P
[HP]
P
[KW]
[A]
0002 1.7 2.6 1 0.75 2 MI3 0.99
0003 2.7 4.2 2 1.5 3.6 MI3 0.99
0004 3.9 5.9 3 2.2 5 MI3 0.99
0006 6.1 9.2 5 4 7.6 MI3 0.99
0009 9 13.5 7.5 5.5 10.4 MI3 0.99
Table 29: Vacon 20 power ratings, 600 V
1
A: Select Fieldbus as remote control place: P2.1 to1 Fieldbus, P3.3 to 3 - Fieldbus
B: Set Modbus RTU protocol to “ON”: SYS P2.2 to 1 – Modbus
2
A. Set Control Word to “0” (2001)
B. Set Control Word to “1” (2001)
C. Frequency converter status is RUN
D. Set Reference value to “5000” (50.00%) (2003)
E. Actual Speed is 5000 (25.00 Hz if MinFreq is 0.00 Hz and MaxFreq is 50.00 Hz)
F. Set Control Word to “0” (2001)
G. Frequency converter status is STOP