Set-up 5
0020200969_07 Set-up instructions 27
7.
Alternatives 2:
Condition: Roof duct without extension
Install the sliding sleeve. ( Page 28)
5.5.4.3 Installing the flat-roof duct
Caution.
Risk of damage to the structure of the
building.
As a result of improper installation, water may
penetrate the building and cause material
damage.
Observe the definitions in the directives
for the planning and implementation of
roofs with seals.
A
B
Ø 125
Ø 120
1
2
3
A Cold roof B Warm roof
1. Determine the installation site for the roof duct.
2. Insert the flat roof penetration collar (2).
3. Glue the flat roof penetration collar firmly in place.
4. Insert the roof duct (1) through the flat roof penetration
collar from above and push it down until seated firmly.
5. Align the roof duct vertically.
6. Secure the roof duct to the roof construction using the
fixing bracket (3).
7. Connect the roof duct to the product using extensions,
elbows and, if required, a sliding sleeve.
If you do not insert a sliding sleeve, you must
always install the 70 mm clamp directly on the
product.
8.
Alternatives 1:
Condition: Roof duct with extension
Install the extensions. ( Page 29)
Install the 45° elbow. ( Page 34)
Install the 87° elbow. ( Page 36)
Install the sliding sleeve. ( Page 28)
Connect all of the pipe joints with air pipe clamps.
( Page 38)
8.
Alternatives 2:
Condition: Roof duct without extension
Install the sliding sleeve. ( Page 28)
5.6 Installing the concentric
connection, 60/100 mm diameter, to the
air/flue system for negative pressure
5.6.1 Installation instructions
Installation example:
Markings have been assigned to the air/flue system in ac-
cordance with EN 1443 and these indicate that the system
complies with the fundamental requirements of the construc-
tion products directive. The air/flue system is not approved
as part of the boiler.
The air/flue gas chimney must be designed and approved for
negative-pressure mode by the manufacturer.
The air/flue gas chimney's data plate is marked for operation
with condensing boilers and a flue gas temperature of at
least 120 °C.
Take into consideration the regulations with regard to fire
resistance.
The Vaillant ecoTEC gas-fired wall-hung boilers that are
mentioned in these installation instructions are approved
in accordance with the European and British standard "PD
CEN/TR 1749: 2005, European scheme for the classification
of gas appliances according to the method of evacuation of
the combustion products (types) C43".
The length of the air/flue pipe must not exceed 1.4 m and
three elbows. This corresponds to a maximum length of 3.4
m for the C43 connection.