USERS GUIDE_______________________________________________________________________
8 ______________________________________________________________________U376EN-1.1
P$
/
/
$
%
&
'
5(/$<
5(/$<
9
287
a
a
9
P$
:::9$,6$/$&20
-98
Figure 6 Electrical connections and jumpers
Power supply requirements
The GMT220 series transmitters are designed to operate with a
nominal 24 VAC/DC supply. The power supply should maintain the
voltage for all load conditions and all mains voltages. The power input
includes a halfwave rectifier. To avoid current peaks, it is
recommended to use a DC supply.
Connection to a 24 VAC supply
The GMT220 series transmitters can also be connected to a 24 VAC
supply without an external rectifier. However, when more than one
transmitter is connected to one 24 VAC transformer, a common loop
is formed and there is an increased risk of a short-circuit. To avoid
this, always use separate floating supply for each transmitter (see
Figure 7 A).
CAUTION
If several transmitters have to share one transformer, the phase ()
must always be connected to + connector in each transmitter (see
Figure 7 B).
&XUUHQWRXWSXW
M
XP
S
HU
P$
5HOD\MXPSHUV
/DQG/
3RZHUVXSSO\
WHUPLQDOV
2XWSXWWHUPLQDOV
5HOD\
WHUPLQDO
5HOD\
WHUPLQDO