Configuration DIP Switches
1
ON
2 3 4
5 6
7
8
Modbus
BACnet
Parity Even
A B C
Parity None
Baud
Rate
Metric
Non-Metric
DIP
Position
Setting
1
Modbus
Modbus protocol in use.
BACnet
BACnet protocol in use.
2-4
A B C
Serial line baud rate
Off
Off
Off
Automatic (default)
Off
Off
On
4800
Off
On
Off
9600
Off
On
On
19200
On
Off
Off
38400
On
Off
On
57600
On On Off 76800
On
On
On
115200
5
Parity Even
Parity even (8E1).
Only affects Modbus protocol.
Parity None
Parity none (8N2).
Only affects Modbus protocol.
6
Non-Metric
Use non-metric units (°F).
Only affects display and service port.
Metric
Use metric units (°C).
Only affects display and service port.
7
Not used
8
Not used