3 INSTALLATION
Selecting Location
When mounting duct model transmitters:
n Avoid installing in a location where condensation may fall on the sensor
inside the duct.
n Position the sensor in the center of the duct.
n Select a site where the transmitter can be installed horizontally, onto the side
of the duct. Do not point the probe downward, as this will make condensation
run down to the sensor.
When mounting wall model transmitters:
n Select a location that represents well the area of interest.
n Do not install on the ceiling.
n Avoid placing the transmitter near heat and moisture sources, close to the
discharge of the supply air ducts, and in direct sunlight.
When mounting outdoor transmitters:
n Install in a location with a good airflow around the transmitter.
n Avoid placing the transmitter near windows, air conditioning units, or other
heat and moisture sources such as cooling towers.
n Install the transmitter at least 2.5 m above ground level.
13