Syntax Description
smode<cr>
Show current start-up operating mode of the
serial line, and prompt to enter new mode.
New mode is taken into use when the device
is reset or powered up.
smode [mode]<cr>
Set serial line start-up operating mode.
Available modes are:
stop =No automatic output. All commands
available. Default mode.
run =Automatic output of measurement
messages. You must stop output with the s
command before entering other commands.
poll = No automatic output. Will respond to
addressed send command and ??
command. You can use other commands
after opening a connection using an
addressed open command.
Example (set device to poll mode):
smode
Serial mode : STOP ? poll
Table 23 Smode Command
Analog output
Syntax Description
aerr ?<cr>
Show currently set analog output error level
for both channels.
aerr<cr>
Show currently set analog output error
levels, prompt to enter new values.
aerr [ch1] [ch2]<cr>
Set error level for both channels without
prompting.
ch1 = error level for analog output channel 1
in mA.
ch2 = error level for analog output channel 2
in mA.
Example (set error level for both analog output channels to 21 mA):
aerr
Ch1 error out : 3.600 I ? 21
Ch2 error out : 3.600 I ? 21
Table 24 Aerr Command