VAMP Ltd Overcurrent and earth-fault relay
Operation and Configuration
VAMP 130
VM130.EN003 Vamp 24h support phone : +358 (0)40 573 6316
19
RESET
Reset the software of the VAMP 130 relay and reset
latches (Reset and Latch)
NOTE!
Disabling a protection function will remove the item from the
menu.
5.3. Setting protection function parameters
The settings of the selected protection functions can be read and
set separately in the submenus of each function.
Available protection stages
I>, I>>, I>>> and I2> (IL SETTING)
Io>, Io>>,Io>>> (Io SETTING)
CBFP (CBFP Set)
5.4. Scaling of measuring transformers
Via the submenus of the SCALING menu the following can be
read and set:
IL SCALING
Current transformer primary value (CTprim)
Current transformer secondary value (CTsec)
Via the submenus of the Io SCALING menu the following can be
read and set:
Io SCALING
Residual current transformer primary value (CToprim)
Residual current transformer secondary value (CTosec)
Residual current input channel 1A or 5A (Ioinp)
5.5. Configuring digital outputs DOUT
Via the submenus of the DOUT menu the following functions
can be read and set:
Configuration of the output signals to the output relays T1 and
T2, A1 – A3 and the operation indicators (LED). Operation
indicators, only VAMPSET.