EasyManua.ls Logo

VAMP 130 - Page 34

Default Icon
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VAMP 130 Overcurrent and earth-fault relay
Technical Description
VAMP Ltd
8
Vamp 24h support phone : +358 (0)40 573 6316 VM130.EN003
SCntr Start counter (Start) reading
TCntr Trip counter (Trip) reading
1-N, 2-N
3-N
Fault type/single-phase fault
e.g.: 1-N = fault on phase L1
1-2, 2-3
1-3
Fault type/two-phase fault
e.g.: 2-3 = fault between L2
and L3
Type
1-2-3 Fault type/three-phase fault
Flt pu Max. value of fault current as
compared to In
Load pu 1 s mean value of pre-fault
phase currents IL1…IL3
Recorded
values
EDly % Elapsed time as compared to
the set operate time, 100% =
tripping
The low-set stage (I>) of the overcurrent unit can be configured
for inverse time characteristic. Four sets of characteristic curves
according to IEC 60255-3 are available for the low-set stage, i.e.:
Normal Inverse (NI), Very Inverse (VI), Extremely Inverse (EI)
ja Long Time Inverse (LTI). The mathematical expressions and
the curve sets are given in Figs. 2.2.1.-3, -4, -5 and -6.
Limitations:
1. The maximum measured current is 50 x I
n
. This limits the
scope of inverse curves when the setting is more than 2.5 x
I
n
. E.g. at setting 4 x I
n
the maximum setting relative current
is 12.5 x I
set
/I
n
although the curves are defined up to 20 x
I
set
/I
n
2. The fastes possible operating time is about 60 ms at inverse
time characteristic according to curve types VI and EI.
Figure 2.2.1-2 Block diagram of the three-phase overcurrent stage I>>.

Table of Contents

Related product manuals