2.4 Typical wiring of ACTpro 1520e/1500e
Label Description Label Description
A Doorcontact,normallyclosed F ACTreaderwirecolourcoding
B Pushtoexit,normallyopen G
Ethernet:RJ45
Note:AllIPdevicemusthaveavalidIPAddress.
C Doornetworks H
Important:Placevaristoracrossalllockterminals.
Note:DiagramshowsnormallyenergisedMagnetic
Lock.
D Controllernetwork J Breakglassunit(doublepole)
E
Breakglassmonitoring,normally
closed
2.4.1 Wiring exit readers
Forclockanddatareaders,wireexitreadersinparallelbutleavethesenselineunconnected.
ForWiegandreaders,wiretheDATA0oftheexitreadertoSENSEontheACTpro1520e.
Maxlength:100mwith12VDC
Cable:8corescreenedBelden9504orequivalent