Page 23
2.4.7 Setup
Once the IC-610 is properly mounted on the wall, open
both faceplates and perform the following steps:
a) Ensure the flat cable is properly connected.
b) Connect the cable wiring of each control
module and sensor to the terminal blocks. The
wiring connections are illustrated in the wiring
diagram provided with the configuration
document.
c) When upgrading your system with a new
configuration, cut out the faceplate labels
supplied with the configuration document and
slide them in the front panel. Then, proceed to
downloading the configuration (refer to
Chapter 3).
d) Close the front panel and the lower access
cover and secure them with the screws
previously removed.
e) Before the adjustment, review Chapter 3 of this
manual for the control descriptions of the IC-
610.
2.5 ALARM CONNECTIONS
The IC-610 provides a normally open and normally
closed dry contact to set off an alarm in case low or high
temperature conditions occur. Moreover, this same
contact can be used to signal a power failure or other
malfunctions. It may be connected to an alarm system or
directly to a siren and / or auto-dialer.
Make the normally closed (NC) or normally open (NO)
connections as indicated in figures 6 and 7.