EasyManua.ls Logo

Varifan IC-610 - Troubleshooting

Default Icon
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 39
SYMPTOM CAUSE REMEDY
Temperature
probe reads
LO
Temperature is
below -6°F (-21°C)
Probe is disconnected
or defective
Check all
connections. If the
problem persists,
and the temperature
is within normal
range, replace the
probe.
Temperature
probe reads
HI
Temperature is above
168°F (76°C)
Probe is short
circuited or defective
Check all
connections. If the
problem persists,
and the temperature
is within normal
range, replace the
probe.
Temperature
average
reads Err
Temperature readings
of the probes used in
the average are too
different and the
control is unable to
calculate a proper
average
Make sure all the
probes are working
properly. If so,
contact your local
distributor
Displays are
blank
Voltage selector
setting is inaccurate
IC-610 is not powered
Ten pin flat cable
between the main and
the top boards of the
IC-610 is
disconnected
Make sure the
control is powered
Make sure the line
voltage selector
switch is properly
set
Make sure the 10
pin flat cable is
connected
Display
reads 88888
and Err
continuously
Configuration memory
integrity has been
compromised
Download the
configuration once
again (refer to
chapter 3)
TROUBLESHOOTING
www.monitrol.com

Related product manuals