Connecting Probe/Sensor Wiring to Consoles TLS-350/ProMax/EMC Consoles
63
TYPE B INTERFACE MODULE - I.S. BAY
Figure 61. Type B Interface Module Wiring
Connecting Devices
Connect sensors in the table below to the appropriate terminals on the Type B Interface module as shown in
Figure 61.
Device Wires Observe Polarity
4SITE solid-state discriminating dispenser
pan sensor
3Yes
4SITE solid-state discriminating containment
sump sensor
3Yes
SENSOR
MAXIMUM
SENSOR
OUTPUT
RATINGS:
13 VDC
.20 AMP
AGB AGBAGBAG BAGB
TYPE B INTERFACE MODULE
1 2 3 4
5
AGB
6
consoles\tbimw.eps
Console
Up to 6
Sensors
Sensor
#1
Sensor
#2
Sensor
#6
ABGABGABG
Attach Cable Shields to Ground
Lug Closest to Conduit Entry
Rigid Conduit
(enters Console
through an I.S. Bay
knockout)