ISD Alarm Message Diagnostics FLOW COLLECT
13
FLOW COLLECT
A 1-Day Vapor Collection Flow Performance Test failure occurs when the vapor collection flow performance is less
than 50%.
ISD MONITORING CATEGORY
Vapor Collection Monitoring for sites equipped with balance vapor recovery systems is responsible for ensuring
that front-end vapor collection is operating within certified range with respect to the baseline collection
performance during fueling events. The baseline collection performance is established by CARB and is the V/L
standard for the system. Among other components, front-end equipment includes the nozzle, hose and the
breakaway. A balance vapor recovery system relies upon a tight bellows seal in order to allow displaced vapors to
return to the UST during fueling events.
DIAGNOSTIC PROCEDURE
Perform the TP201.4 test.
Find the hose that triggered the alarm by looking at the Collection Tests in the ISD Daily Report in the normal
menu.
Refer to the Clear Test Repair Menu (on page 36) for clearing this alarm on the TLS after repairs are complete.
FIELD NOTES
This alarm should not occur at a Healy Assist site. If it does check EVR Type setup in ISD.

Table of Contents

Other manuals for Veeder-Root TLS-350R PLUS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-350R PLUS and is the answer not in the manual?

Veeder-Root TLS-350R PLUS Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS-350R PLUS
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals