In-Tank Alarms
MMM DD, YYYY HH:MM XM
T1 : OVERFILL ALARM
---- IN-TANK ALARM ----
T 1:REGULAR UNLEADED
OVERFILL ALARM
MMM DD, YYYY HH:MM XM
consoles\qh\US\16.eps
MMM DD, YYYY HH:MM XM
T1 : LOW PRODUCT ALARM
---- IN-TANK ALARM ----
T 1:REGULAR UNLEADED
LOW PRODUCT ALARM
MMM DD, YYYY HH:MM XM
consoles\qh\US\17.eps
CAUSE:
Fuel level in the tank shown has exceeded the
Overfill Level during a delivery.
ACTION:
Stop the delivery immediately!
Silence the alarm by pressing the red ALARM/
TEST key.
CAUSE:
Fuel level in the tank shown has dropped
below the Low Product Alarm level.
ACTION:
Silence the alarm by pressing the red ALARM/
TEST key.
Arrange a delivery.
MMM DD, YYYY HH:MM XM
T1 : LEAK ALARM
---- IN-TANK ALARM ----
T 1:REGULAR UNLEADED
LEAK ALARM
MMM DD, YYYY HH:MM XM
consoles\qh\US\18.eps
MMM DD, YYYY HH:MM XM
T1 : HIGH WATER ALARM
---- IN-TANK ALARM ----
T 1:REGULAR UNLEADED
HIGH WATER ALARM
MMM DD, YYYY HH:MM XM
consoles\qh\US\19.eps
CAUSE:
Fuel loss has exceeded the pre-programmed
limit during a leak test in the tank shown.
This indicates a possible leak.
ACTION:
Silence the alarm by pressing the red
ALARM/TEST key. Contact your VR Service
Contractor for advice.
CAUSE:
Water at the bottom of the tank shown has
exceeded the High Water Alarm level.
ACTION:
Close all pumps attached to this tank.
Silence the alarm by pressing the red
ALARM/TEST key. Contact your VR Service
Contractor for advice.