KEY SYMBOLS:
Press until the display shows:
To test individual tanks press . To test all tanks press the display will show
To end the test manually press or to set a duration for the test press .
Select the test accuracy, either 0.20 gal/hr or 0.10 gal/hr. To change the setting press . Press to continue.
Enter the Test Duration in hours, press . The display will show
Press to start the test. For individual tanks press to go to the next tank.
Return to normal operating mode: press until the date and time display appears.
F
START IN-TANK LEAK TEST
PRESS <STEP> TO CONTINUE
consoles\qh\44.eps
S
C
E
S S S
TEST CONTROL: ALL TANKS
TIMED DURATION
consoles\qh\45.eps
C
E
S
S
C
E
S
E
S
START LEAK TEST TANKS
PRESS <ENTER>
consoles\
q
h\46.eps
E
T
F
To Start An In-Tank Leak Test
Do not start an in-tank leak test if there has been a
delivery to the tank to be tested within the previous
8 hours. This will result in an invalid test.
A delivery to a tank being tested results in an invalid
test.
Dispensing from a tank being tested will cause a
Sudden Loss Alarm.