Function Code: 881 Version 1
Function Type: Set Communication Port Data
Command Format: Inquire:
Display: <SOH>S881PPBBBBBPSDTAA <SOH>I881PP
Computer: <SOH>s881PPBBBBBPSDTAA <SOH>i881PP
Notes:
1. PP - Communication Port Number (Decimal 01-05). Inquiry commands
work for all 5 ports (Decimal 01-05). Set commands only work
for the first 3 ports (Decimal 01-03).
Typical Response Message, Display Format:
<SOH>
I88101
22-05-01 15:11
PORT SETTINGS:
COMM 1 : SERIAL
232 SECURITY CODE : 000000
STATUS : DISABLED
BAUD RATE : 9600
PARITY : ODD
STOP BIT : 1
DATA LENGTH : 7
HANDSHAKE : NONE
<ETX>
Typical Response Message, Computer Format:
<SOH>i881PPYYMMDDHHmmPPBBBBBPSDTAA&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. BBBBB - Baud Rate (Decimal)
3. P - Parity (Decimal; 0=None, 1 or 2)
4. S - Stop Bit (Decimal; 1 or 2)
5. D - Data Bit (Decimal; 7 or 8)
6. T - Pulse or Tone (Decimal; 0=Tone, 1=Pulse)
7. AA - Number of Rings before Answer (Decimal)
8. && - Data Termination Flag
9. CCCC - Message Checksum