Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 46
7.2.3 I/O DEVICE REPORTS
Function Code:
406 Version 1
Function Type: Relay Status Report
Command Format:
Display: <SOH>I406RR
Computer: <SOH>i406RR
Typical Response Message, Display Format:
<SOH>
I40600
22-05-01 14:57
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
RELAY STATUS: OPEN
<ETX>
Typical Response Message, Computer Format:
<SOH>i406RRYYMMDDHHmmRRssss...
RRssss&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. RR - Relay Number (Decimal, 00 = all)
3. ssss - Relay Status:
0001 - Relay Open
0002 - Relay Closed
4. && - Data Termination Flag
5. CCCC - Message Checksum