Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 25
7.2.2 IN-TANK REPORTS
Function Code:
201 Version 1
Function Type: In-Tank Inventory Report
Command Format:
Display: <SOH>I201TT
Computer: <SOH>i201TT
Typical Response Message, Display Format:
<SOH>
I20101
22-05-01 14:56
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
INVENTORY REPORT
TANK PRODUCT VOLUME TC VOLUME ULLAGE HEIGHT WATER TEMP
1 REGULAR UNLEADED 5329 5413 4699 48.97 0.00 37.39
<ETX>
Typical Response Message, Computer Format:
<SOH>i201TTYYMMDDHHmmTTpssssNNFFFFFFFF...
TTpssssNNFFFFFFFF...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. p - Product Code (single ASCII character, from 20 Hex - 7E Hex)
4. ssss - Tank Status Bits:
Bit 1 - (LSB) Delivery in Progress
Bit 2 - Leak Test in Progress
Bit 3 - Invalid Fuel Height Alarm (MAG Probes Only)
Bit 4-16 - Unused
5. NN - Number of eight character Data Fields to follow (Hex)
6. FFFFFFFF - ASCII Hex IEEE float:
1. Volume
2. TC Volume
3. Ullage
4. Height
5. Water
6. Temperature
7. Water Volume
7. && - Data Termination Flag