Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 117
Function Code: 884 Version 1
Function Type: Set Serial Handshaking Method
Command Format: Inquire:
Display: <SOH>S88400f <SOH>I88400
Computer: <SOH>s88400f <SOH>i88400
Notes:
1. Inquiry and Set commands work for the first 3 ports (Decimal
01-03). The ports can be set to the following values:
Port 1: 0 = None, 1 = XON/XOFF, 2 = Hardware
Port 2 & 3: 0 = None, 1 = XON/XOFF
Typical Response Message, Display Format:
<SOH>
I88401
22-05-01 15:11
HANDSHAKE : NONE
<ETX>
Typical Response Message, Computer Format:
<SOH>i88400YYMMDDHHmmf&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. f - Handshaking Flag: Sets handshaking method for port on which
command is received
0 = None
1 = XON/XOFF
2 = Hardware
3. && - Data Termination Flag
4. CCCC - Message Checksum