EasyManuals Logo

Veeder-Root TLS2 Serial Interface Manual

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #130 background imageLoading...
Page #130 background image
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 127
Function Code: 8C3 Version 4
Function Type: Set TCP/IP Subnet Mask Address
Command Format: Inquire:
Display: <SOH>S8C300aaa.aaa.aaa.aaa <SOH>I8C300
Computer: <SOH>s8C300AAAAAAAA <SOH>i8C300
Notes:
1.aaa.aaa.aaa.aaa - Subnet Mask Address (decimal)
2. AAAAAAAA - Subnet Mask IP Address (ASCII hex, two digits represent each
field)
Typical Response Message, Display Format:
<SOH>
S8C300
JUL 31, 2008 9:02 AM
TCPIP SETUP PARAMETERS
SUBNET MASK ADDRESS: 255.255.255.0
<ETX>
Typical Response Message, Computer Format:
<SOH>s8C300YYMMDDHHmmvAAAAAAAA&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. v - Valid Data Flag
0 = Not Valid
1 = Valid
3. AAAAAAAA - Subnet Mask (ASCII hex, two digits represent each field)
4. && - Data Termination Flag
5. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS2 and is the answer not in the manual?

Veeder-Root TLS2 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS2
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals