Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 141
Function Code: A02 Version 1
Function Type: Probe Factory Calibration Values
Command Format:
Display: <SOH>IA02TT
Computer: <SOH>iA02TT
Typical Response Message, Display Format:
<SOH>
IA0201
22-05-01 15:12
TANK 1 REGULAR UNLEADED MAG GRADIENT = 180.0000 OPT= 0x0000
<ETX>
Typical Response Message, Computer Format:
<SOH>iA02TTYYMMDDHHmmTTpPPNNFFFFFFFF...
TTpPPNNFFFFFFFF...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. p - Product Code (single ASCII character, from 20 Hex - 7E Hex)
4. PP - Probe Type:
00 - Unknown (no further data follows for this probe)
03 - MAG
5. NN - Number of eight character Data Fields to follow (Hex)
6. FFFFFFFF - Probe Data (ASCII Hex IEEE float)
7. && - Data Termination Flag
8. CCCC - Message Checksum