EasyManua.ls Logo

Veeder-Root TLS2 - Page 148

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 145
Function Code: A13 Version 1
Function Type: Probe Long Term Average Buffers
Command Format:
Display: <SOH>IA13TT
Computer: <SOH>iA13TT
Typical Response Message, Display Format:
<SOH>
IA1301
22-05-01 15:13
TANK 1 REGULAR UNLEADED MAG NUMBER OF SAMPLES = 424
569.000 13584.000 13584.000 13584.000 13584.000 13585.000 13585.000 13584.000
13584.000 13585.000 13584.000 40000.000 21993.000 21993.000 21993.000 21993.000
21993.000 21993.000 40000.000
<ETX>
Typical Response Message, Computer Format:
<SOH>iA13TTYYMMDDHHmmTTpPPSSSSNNFFFFFFFF...
TTpPPSSSSNNFFFFFFFF...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. p - Product Code (single ASCII character, from 20 Hex - 7E Hex)
4. PP - Probe Type:
00 - Unknown (no further data follows for this probe)
03 - MAG
5. SSSS - Number of Samples (Hex)
6. NN - Number of eight character Data Fields to follow (Hex)
7. FFFFFFFF - Probe Data (ASCII Hex IEEE float)
8. && - Data Termination Flag
9. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2

Related product manuals