EasyManua.ls Logo

Veeder-Root TLS2 - Rigid Conduit Wiring Run

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 27
Function Code: 203 Version 1
Function Type: In-Tank Leak Detect Report
Command Format:
Display: <SOH>I203TT
Computer: <SOH>i203TT
Typical Response Message, Display Format:
<SOH>
I20301
22-05-01 14:56
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
IN-TANK LEAK TEST REPORT
T 1 REGULAR UNLEADED
TEST STATUS: OFF 0.20 GAL/HR TEST PASS
TEST STARTING TIME: 19-05-01 10:30 PM TEST LENGTH: 3.0 HOURS
START TEMP: 58.7 DEG F START VOLUME: 2123.2 GAL
END TEMP: 58.1 DEG F LEAK RATE: -0.01 GAL/HR
CUMULATIVE PERIODIC VOLUME CHANGE (GAL):
-0.01 -0.02 -0.01 -0.03 -0.05 -0.04
<ETX>
Typical Response Message, Computer Format:
<SOH>i203TTYYMMDDHHmmTTpYYMMDDHHmmHHNNFFFFFFFF...
TTpYYMMDDHHmmHHNNFFFFFFFF...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. p - Product Code (single ASCII character, from 20 Hex - 7E Hex)
4. YYMMDDHHmm - Starting Date/Time
5. HH - Test Duration (hours)
6. NN - Number of eight character Data Fields to follow (Hex)
7. FFFFFFFF - ASCII Hex IEEE float:
1. Starting Temp
2. Ending Temp
3. Starting Volume
4. Ending Rate
5. Hourly changes up to the number of fields
8. && - Data Termination Flag
9. CCCC - Message Checksum