EasyManuals Logo

Veeder-Root TLS2 Serial Interface Manual

Veeder-Root TLS2
165 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 36
Function Code: 20D Version 1
Function Type: In-Tank Stick Height Report
Command Format:
Display: <SOH>I20DTT
Computer: <SOH>i20DTT
Notes:
1. This command will respond only if stick height is enabled.
Tank stick height is fuel height (without tilt) + stick
offset. If the stick height is less then zero, it will be
set to zero. If the stick height is greater than tank
diameter, it will be set to tank diameter.
Typical Response Message, Display Format:
<SOH>
I20D01
22-05-01 14:57
STATION HEADER 1....
STATION HEADER 2....
STATION HEADER 3....
STATION HEADER 4....
TANK STICK HEIGHT
TANK PRODUCT LABEL INCHES
1 REGULAR UNLEADED 79.24
<ETX>
Typical Response Message, Computer Format:
<SOH>i20DTTYYMMDDHHmmTTFFFFFFFF...
TTFFFFFFFF&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. FFFFFFFF - Stick Height (ASCII Hex IEEE float)
4. && - Data Termination Flag
5. CCCC - Message Checksum

Other manuals for Veeder-Root TLS2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS2 and is the answer not in the manual?

Veeder-Root TLS2 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS2
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals