Serial Interface Manual
• TLS2 Monitoring Systems
Part No. 577013-767, Revision H 63
Function Code: 52C Version 1
Function Type: Set Receiver Auto Dial On Alarms
Command Format: Inquire:
Display: <SOH>S52CRRAANNTTSS <SOH>I52CRR
Computer: <SOH>s52CRRAANNTTSS <SOH>i52CRR
Typical Response Message, Display Format:
<SOH>
I52C01
22-05-01 15:06
RECEIVER SETUP REPORT
RECEIVER : 01
IN-TANK ALARMS :
T 1:MAX PRODUCT
T 1:DELIVERY NEEDED
<ETX>
Typical Response Message, Computer Format:
<SOH>i52CRRYYMMDDHHmmRRnnAANNTTSS...
RrnnAANNTTSS...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. RR - Receiver Number (Decimal, 01 only)
3. nn - Number of Alarms to Follow (Hex)
4. AA - Alarm/Warning Category:
02 = Tank Alarm
5. NN - Alarm Type Number:
- If AA is 02 and NN is:
03 = Tank High Water Alarm
04 = Tank Overfill Alarm
05 = Tank Low Product Alarm
08 = Tank Invalid Fuel Level Alarm
09 = Tank Probe Out Alarm
11 = Tank Delivery Needed Warning
12 = Tank Maximum Product Alarm
13 = Tank Gross Leak Test Fail Alarm
14 = Tank Periodic Leak Test Fail Alarm
15 = Tank Annual Leak Test Fail Alarm
27 = Tank Cold Temperature Warning
6. TT - Tank/Sensor Number (Decimal, 00 = all)
7. SS - Status (Hex):
00 = Clear
01 = Set
8. && - Data Termination Flag
9. CCCC - Message Checksum