Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 78
Function Code: 579 Version 5
Function Type: Set Tank Idle Delivery Enabled
Command Format: Inquire:
Display: <SOH>S57900f <SOH>I57900
Computer: <SOH>s57900f <SOH>i57900
Typical Response Message, Display Format:
<SOH>
I57900
22-05-08 15:02
TANK IDLE DELIVERY
ENABLED
<ETX>
Typical Response Message, Computer Format:
<SOH>i57900YYMMDDHHmmf&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. f - Tank Idle Delivery flag
0 = Disabled
1 = Enabled
3. && - Data Termination Flag
4. CCCC - Message Checksum