Serial Interface Manual
TLS2 Monitoring Systems
Part No. 577013-767, Revision H 91
Function Code: 610 Version 1
Function Type: Set Tank Delivery Delay
Command Format: Inquire:
Display: <SOH>S610TTdd <SOH>I610TT
Computer: <SOH>s610TTdd <SOH>i610TT
Typical Response Message, Display Format:
<SOH>
I61001
22-05-01 15:08
TANK DELIVERY DELAY
TANK PRODUCT LABEL
1 REGULAR UNLEADED 1
<ETX>
Typical Response Message, Computer Format:
<SOH>i610TTYYMMDDHHmmTTdd
TTdd&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. dd - Indicates the length of time in minutes (01-99)
4. && - Data Termination Flag
5. CCCC - Message Checksum