24
6 Supplement
FIBERTRAC 31 • Four-wire 4 … 20 mA/HART
62067-EN-211203
6 Supplement
6.1 Technical data
Note for approved instruments
The technical data in the respective safety instructions which are included in delivery are valid for
approvedinstruments(e.g.withExapproval).Thesedatacandierfromthedatalistedherein,for
exampleregardingtheprocessconditionsorthevoltagesupply.
All approval documents can be downloaded from our homepage.
Electromechanical data - version IP66/IP67
Options of the cable entry
Ʋ Cable entry M20x1.5;½NPT
Ʋ Cable gland M20x1.5;½NPT(cablediameterseebelowtable)
Ʋ Blind plug M20x1.5;½NPT
Ʋ Closing cap ½NPT
Material ca-
ble gland
Material seal
insert
Cable diameter
4.5 … 8.5 mm 5 … 9 mm 6 … 12 mm 7 … 12 mm 10 … 14 mm
PA NBR
Brass,nickel-
plated
NBR
Stainless
steel
NBR
Flammability class - Supply lines at least VW-1
Wire cross-section (spring-loaded terminals)
Ʋ Massivewire,strandedwire 0.2 … 2.5 mm² (AWG 24 … 14)
Ʋ Stranded wire with end sleeve 0.2 … 1.5 mm² (AWG 24 … 16)
Voltage supply
Operating voltage 24 … 65 V DC (-15 … +10 %) or 24 … 230 V AC
(-15…+10%),50/60Hz
Reverse voltage protection Available
Max.powerconsumption 6 VA (AC); 4 W (DC)