10 Supplement
VEGAPULS 61 • Modbus and Levelmaster protocol
41717-EN-160224
ScadaPack
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
3
2
45
5
2
1
3
4
9
6
7
8
2off
on
( )
(
)
(-)
(-)
+8 +30
Vdc
to
GND
COM Part 3 (C3)
RS485
TXD-
TXD+
GND
Fig. 58: Connection of VEGAPULS 61 to RTU ScadaPack
1 VEGAPULS 61
2 RTU ScadaPack
3 Voltage supply
Parameter
Parameter Value
Baud Rate 9600
Floating Point Format Code 0
RTU Data Type Floating Point
Input Register Base Number 30001
The basic number of the input registers is always added to the input register address of VEGAPULS
61.
Address 31303 must hence be entered as register address for 1302 for RTU ScadaPack.
10.7 Radio astronomy stations
Certain requirements for the use outside closed vessels result from the radio license for Europe of
VEGAPULS61.Youcanndtherequirementsinchapter"Radio license for Europe". Some of these
requirements refer to radio astronomy stations. The following table states the geographic positions
of radio astronomy stations in Europe:
Country Name of the Station Geographic Latitude Geographic Longitude
Finland Metsähovi 60°13'04'' N 24°23'37'' E
Tuorla 60°24'56'' N 24°26'31'' E