62
8 Diagnosis, asset management and service
VEGAPULS 61 • Modbus and Levelmaster protocol
41717-EN-160224
Code
Text message
Cause Rectication DevSpec State in CMD
48
M500
Error with the reset deliv-
ery status
– With the reset to delivery
status, the data could
not be restored
– Repeat reset
– LoadXMLlewithsen-
sor data into the sensor
Bit 0 of Byte 14…24
M501
Error in the non-active lin-
earizationtable
– Hardware error
EEPROM
– Exchanging the elec-
tronics
– Send instrument for
repair
Bit 1 of Byte 14…24
M502
Error in the diagnosis
memory
– Hardware error
EEPROM
– Exchanging the elec-
tronics
– Send instrument for
repair
Bit 2 of Byte 14…24
M503
Meas. reliability too low
– The echo/noise ratio
is too small for reliable
measurement
– Check installation and
process conditions
– Clean the antenna
– Change polarisation
direction
– Use instrument with
higher sensitivity
Bit 3 of Byte 14…24
M504
Error on an device inter-
face
– Hardware defect – Check connections
– Exchanging the elec-
tronics
– Send instrument for
repair
Bit 4 of Byte 14…24
M505
No echo available
– Level echo can no
longer be detected
– Clean the antenna
– Use a more suitable
antenna/sensor
– Remove possible false
echoes
– Optimizesensorposition
and orientation
Bit 7 of Byte 14…24
8.4 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
Therstmeasuresare:
•
Evaluation of fault messages, for example via the display and
adjustment module
•
Checking the output signal
•
Treatment of measurement errors
Further comprehensive diagnostics options are available with a PC
with PACTware and the suitable DTM. In many cases, the reasons can
bedeterminedinthiswayandfaultsrectied.
The below tables show typical examples of application-related meas-
urementerrorswithliquids.Themeasurementerrorsaredierentiated
according to the following:
Reaction when malfunc-
tion occurs
Procedur
e for fault recti-
cation
Treatment of measure-
ment errors with liquids