EasyManua.ls Logo

Velocity PHANTOM II - Page 53

Velocity PHANTOM II
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
53110331-01 - 5/20
PHTM II
Installation, Operating & Service Instructions
16 Operation (continued)
Operating Mode
Basic boiler status is displayed and DHW setpoint
may be adjusted.
Figure 16-3:Viewing boiler status
Press "" or "" buttons to cycle through Status List.
Each item will alternate between status code and its
corresponding value.
Table 16-4: Status List
Display Description
StA
Status (see Table 16-5)
SP
Active, Operating Setpoint
bt
Boiler Supply Temperature
rt
Boiler Return Temperature
dt
DHW Temperature
dr
DHW Flow Rate
Ft
Flue Temperature
ot
Outdoor Air Temperature*
ht
Recirculation (header*)
Temperature
Fr
Firing Rate
rUn
Run Time Hours
CYC
Boiler Cycles
H##
Hold or Warning Condition
E##
Manual Reset Lockout
* Not available with local user display
The STA (status) display code contains below listed
values. This list is also available on display door label.
Table 16-5 Managing of Status Numbers
Display
Description (see Section 19
Troubleshooting for explanation)
0
Self Check
1
Standby
2
Waiting For Air Pressure Switch To Close
3
Prepurge
4
Burner Ignition
5
Calibration
6
Low Fire Hold
7
Rate Limit
8
Run (Modulate)
9
Postpurge
10
Pump air elimination (2 minutes)
11
Standby Delay
12
Lockout
13 Boiler On/Off Switch (A01)
14
Warm Weather Shutdown*
*
+
* Not available with local user display.
+

Figure 16-6: Adjusting DHW Setpoint
Press "+" or "-" buttons to immediately change the
DHW setpoint. Faucet and DHW Setpoint flash while
editing.
reset
reset

Other manuals for Velocity PHANTOM II

Related product manuals