August 11, 2016
2 INSTALLING THE FORECOURT
C
ONTROLLER INTERFACE BOX
This chapter provides instructions for installing the Forecourt Controller
Interface (FCI) box.
You can install the FCI box with
• Up to four current loop boards
• Up to four RS485 boards
• Any combination of current loop boards and RS485 boards (up to four
boards)
Warning:Before you begin to install the Forecourt Controller Interface box,
be sure all power to the existing distribution box and PAM or
Electronics Cabinet is disconnected at the main panel. Multiple
disconnects may be required to de-energize these devices. (Refer to
the General Requirements section in Chapter 1.)
Determining a Location
The Forecourt Controller Interface box must be mounted in an indoor location.
Locate the box at least 18 inches above the floor in an area where liquids will
not be spilled onto it.
Note: The Forecourt Controller Interface box is to be mounted in an indoor
location only. The box is not to be used in a hazardous location. Do not
mount the Forecourt Controller Interface in a fuel dispenser.
Avoid the following locations:
• DO NOT install less than six inches near or inside electrical panels
• DO NOT install less than six inches near submersible pump controllers or
along side wiring to these devices
• DO NOT install less than six inches near submersible pump relays