22 Forecourt Controller Interface Installation Guide
August 11, 2016
2. For mounting into drywall, use four 1/8-inch toggle bolts, 3 inches long.
To install the toggle bolts:
a. Open a hole of the recommended size (usually 3/8 or 1/2 inch) at the
center of the holes marked in step 2.
b. Mount the toggle bolts to the pre-drilled tabs on the unit.
c. Push the toggle bolts through the wall hole and tighten securely.
Connecting the Dispenser Control Cables
Note: Before connecting the dispenser control cables to the FCI box, the
Megger Test must be used. The Megger Test checks the quality of the
cable insulation. The dispenser control cables routed from the dispenser
to the FCI box must not be less than six inches to the proximity of power
or other data cables.
Dispensers are connected to the FCI using the existing dispenser control cables
previously connected to the distribution box.
1. Locate the dispenser control cables previously removed from the
distribution box.
2. Do one of the following:
– For Gilbarco dispensers, remove the wire nuts that connect the
dispenser control wires to the existing distribution box connectors.
Set aside the wire nuts for reuse.
– For Wayne dispensers, strip 1/2-inch of insulation from each wire on
the dispenser control cable twisted pair, if not already stripped.