41VERTIV™ - Liebert
®
EFC - UM - 10040805MAN_ENG - 30.03.2023



as R407C, R134a, R410A), have to comply with the F-gas Regulation (EU) No. 517/2014.
This Regulation is in force since Jan 1, 2015 an it replaces the Re. (EU) no. 342/2006.
This document summarizes the obligations for the operators that are responsible for the equipment during all its operative life until its
disposal.

 517/2014
Regulation (EU) No 517/2014 of the European Parliament and of the Council of 16 April 2014




2015/2067
Commission Implementing Regulation (EU) 2015/2067 of 17 November 2015 establishing,
pursuant to Regulation (EU) No 517/2014 of the European Parliament and of the Council,

persons as regards stationary refrigeration, air conditioning and heat pump equipment, and





1516/2007
Commission Regulation No 1516/2007 of 19 December 2007 establishing, pursuant to
Regulation (EC) No 842/2006 of the European Parliament and of the Council, standard leakage
checking requirements for stationary refrigeration, air conditioning and heat pump equipment




1497/2007
Commission Regulation No 1497/2007 of 18 December 2007 establishing, pursuant to
Regulation (EC) No 842/2006 of the European Parliament and of the Council, standard leakage
         
greenhouse gases
From 01/01/2017 to be replaced by:
Commission Implementing Regulation (EU) 2015/2068 of 17 November 2015 establishing,
pursuant to Regulation (EU) No 517/2014 of the European Parliament and of the Council, the


Following notes have to be considered when operating with the above mentioned equipments:
Fluorinated greenhouse gases are covered by the Kyoto Protocol.

Referring to the value noted in chapter 8.9 of Regulation (EU) No 517/2014. Here below the global warming potential (GWP) of some
major F-gases or mixtures:
R-134a GWP 1430
R-407C GWP 1774
R-410A GWP 2088
 the refrigerants as R22 are not F-gas and their relevant regulation is Reg. (EU) no. 1005/2009.


Operator, according to Regulation 517/2014 Article 2, point 8, means the natural or legal person exercising actual power over the technical
functioning of products and equipment covered by this Regulation.

Where large installations are involved, service companies are contracted to carry out maintenance or servicing. In these cases the
determination of the operator depends on the contractual and practical arrangements between the parties.

         
feasible and do not entail disproportionate cost:
a Prevent leakage of these gases and as soon as possible repair any detected leakage.
b 
