A - 1VERTIV™ - Liebert
®
EFC - UM - 10040805MAN_ENG - 30.03.2023
Enclosure A - Technical data table
2
Evaporative Cooling Fans +
Pump
400 V / 3 Ph + N
/ 50 Hz + earth
100 112 150 35
Evaporative Cooling + DX Fans
+ Pump + Compressor(s)
400 V / 3 Ph + N
/ 50 Hz + earth
134(168)
**
274(308)
**
150 (200) 50
Evaporative Cooling Fans +
Pump
400 V / 3 Ph + N
/ 50 Hz + earth
178,2 196,2 200 70
Evaporative Cooling + DX Fans
+ Pump + Compressor(s)
400 V / 3 Ph + N
/ 50 Hz + earth
212.2
(246.2)
**
352.2
(386.2)
**
250 95
Evaporative Cooling Fans +
Pump
400 V / 3 Ph + N
/ 50 Hz + earth
147 159 150 70
Evaporative Cooling + DX Fans
+ Pump + Compressor(s)
400 V / 3 Ph + N
/ 50 Hz + earth
181
(215)**
321
(355)**
200 (250) 70 (95)
Evaporative Cooling Fans +
Pump
EFC400
400 V / 3 Ph + N
/ 50 Hz + earth
150 168 200 50
Evaporative Cooling + DX Fans
+ Pump + Compressor(s)
EFC400
400 V / 3 Ph + N
/ 50 Hz + earth
(218)**
((286))***
(358)**
((426))***
(250)**
((300))***
(95)**
((150))***
Evaporative Cooling Fans +
Pump
EFC440
400 V / 3 Ph + N
/ 50 Hz + earth
168.8 186.8 200 70
Evaporative Cooling + DX Fans
+ Pump + Compressor(s)
EFC440
400 V / 3 Ph + N
/ 50 Hz + earth
(236.8)**
((304.8))***
(376.8)**
((444.8))***
(250)**
((350))***
(120)**
((185))***
* Only universal (type B, B+) RCD protective devices are permitted;
** value in brackets is for tandem compressors;
*** value in dual brackets is for dual tandem compressors.
1. The cables have to be sized in compliance with local standards and according to the type and characteristics (e.g. Ampere) of installation.
2. Value of cable size is related to PVC insulation, 40°C ambient temperature and unipolar cable type.
3. The data in the tables do not consider the absorbed current for other options not explicitly described.
4. The specic energy allowed to ow from the circuit breakers, installed by the user, must be lower than 300.000A
2
x s.
5. Prescriptions on the dierential relay required to the user:
• For special places (healthcare facilities, etc...) comply with the local regulations;
• For ordinary places, a low sensitivity is suggested (300mA) coordinated with the value of the ground heater (IEC 364): Ra ≤ 50/Ia (Art.413.1.4.1,
CEI 64-8 or IEC60364-4-45);
• In case of frequent over-voltages with mains impulse, it is advisable to install a selective dierential and to evaluate the need for adopting other
devices.