The UPS will update the anticipated run time calculation only under certain conditions.
The UPS must have a steady load that is greater than 20%.
The UPS must be at 100% charge at the start of a battery discharge.
The battery discharge must continue uninterrupted until the batteries reach their end-of-discharge voltage.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in Table 12.8 on page63 will
be restored. This will override any value that is Auto-Learned.
Vertiv | Lieber GXT3 Installer/User Guide | 65